Clariti Public sample calculation report

Real Clariti result · public sample

Cast-in-channel calculation check

This sanitized sample presents the inputs, evaluated results and key assumption from a real Clariti design. It omits the private project and is not a manufacturer approval or a substitute for project-specific engineering review.

✓ Calculation checked

CPRO50-350 with M20 bolts

18 of 18 evaluated checks passed. The governing check was shear with lever arm at 99% utilisation.

18/18checks passed

Design inputs

Concrete
C30/37, cracked
Reinforcement
Widely spaced
Member thickness
250 mm
Edge distance
75 mm
Channel
CPRO50-350
Bolt
M20
Lever arm
110 mm
Calculation basis
EN 1992-4
Applied loads and positions
LoadPositionTensionShear
1 75 mm 3.25 kN 5.0 kN
2 225 mm 3.25 kN 5.0 kN

Assumption requires confirmation

The passing result uses a restraint factor of αM = 2, assuming full rotational fixity at the bolt-to-bracket connection. If that connection cannot justify full fixity, this option should not be specified without redesign.

All 18 evaluated checks

The percentages below are utilisation values from the Clariti result. All evaluated checks passed.

Tension
Ref. Check Utilisation Result
3.1 Steel Failure - Anchor in Tension 13% Pass
3.2 Steel Failure - Connection 15% Pass
3.3 Steel Failure - Channel Lips 13% Pass
3.4 Steel Failure - Channel Bolt 4% Pass
3.5 Steel Failure - Channel Flexure 6% Pass
3.6 Pull Out Failure 10% Pass
3.7 Concrete Cone Failure 27% Pass
3.8 Splitting Failure 23% Pass
Shear
Ref. Check Utilisation Result
4.2 Steel Failure - Anchor in Shear 12% Pass
4.3 Steel Failure - Connection Shear 14% Pass
4.4 Steel Failure - Channel Lips (Shear) 15% Pass
4.5 Steel Failure - Channel Bolt (Shear with Lever Arm) 99% Pass
4.6 Concrete Pry Out 21% Pass
4.7 Concrete Edge Failure 83% Pass
Combined
Ref. Check Utilisation Result
7.1 Steel Failure - Channel Bolt (Combined) 97% Pass
7.2 Steel Failure - Channel Lips & Flexure (Combined) 4% Pass
7.3 Steel Failure - Anchor & Connection (Combined) 4% Pass
7.4 Concrete Failure (Combined Loads) 90% Pass

Non-applicable checks

Clariti marked these six checks as skipped; they are not included in the 18 evaluated checks.

  • Concrete Blow Out Failure
  • Steel failure of supplementary tensile reinforcement
  • Anchorage failure of supplementary tensile reinforcement
  • Steel Failure - Channel Bolt (Shear without lever arm)
  • Supplementary Reinforcement - Steel Failure
  • Supplementary Reinforcement - Anchorage Failure

Before and after

Original proposalCPRO38-300 · M12 · 120 mm lever arm3 failed checks
Clariti resultCPRO50-350 · M20 · 110 mm lever arm18/18 evaluated checks passed

Clariti retained the 75 mm edge distance, 250 mm concrete member, original load positions and applied loads while testing practical changes to the channel, bolt, restraint and lever arm.